Design a reinforced concrete (RC) short column with axial load

PROCEDURE

Configuration:

  • Configure the parameters such as working load (KN), grade of concrete, grade of steel, unsupported length lx (m), unsupported length ly (m) and support conditions.
  • Proceed to the next step by clicking on the next arrow.
  • Calculate factored load (Pu), effective lengths lxeff and lyeff in mm. After three incorrect attempts, correct formula and value will be displayed.
  • Proceed to the next step by clicking on the next arrow.

Calculations:

  • Assume and enter the value of Asc within the range of 0.8% to 6% as per IS 456:2000, Clause 26.5.3.1 a. Values of Ag, Ac and Asc will be displayed.
  • Select the type of column. Proceed to the next step by clicking on the next arrow.
  • Enter the value of b/D ratio. After clicking on submit button, checks for short column and axially loaded column along with dimensions of column are displayed.
  • Proceed to the next step by clicking on the next arrow.
  • Enter the diameter of longitudinal bar which should be more than or equal to 12 mm as per IS 456:2000, Clause 26.5.3.1 d.
  • Enter the number of bars. Enter the diameter of lateral ties to be provided. Enter the value of cover to be provided in mm.